Liquid-cooled Cabinet

System Features


Technical Parameters

SU3441E3440MV


  • System Model

    SU3441E3440MV

  • C-rate

    1C

  • Medium Voltage Power Station

     

  • Power of MV Station

    3440KVA

  • Transformer

     

  • Rated Power

    3440KVA

  • Nominal Voltage

    6~35kV

  • No. of phases

    3

  • Frequency

    50/60Hz

  • Rmu

     

  • Switch Configuration

    Breaker/Load Switch + Fuse Combination

  • Insulating Medium

    SF6

  • Voltage Range

    6~35kV

  • Auxiliary Transformer

     

  • Nominal Power

    100KVA

  • Converter

     

  • Rated Power

    1725kW

  • DC Voltage Range

    1500Vdc

  • AC Rated Voltage

    690Vac

  • Maximum Efficiency

    99%

  • Quantity

    2

  • Anti-Corrosion

    C4

  • IP Rating

    IP55

  • Dimensions (W×H×D)

    6058×2896×2438mm

  • Weight

    18,000Kg

  • Compliance

    GB17467,IEC62271-202

  • Communication interfaces

    RS485/CAN/Ethernet

  • Communication protocols

    Modbus-RTU/ModbUS-TCP/IEC61850/IEC104

  • Operating Temperature Range

    -25℃-60℃

  • Max. Working Altitude

    4000m


DC Side Option (1)
  • Cabinet Option

     

  • Nameplate Energy

    344.064kWh

  • Dimension (W×H×D)

    1300x2428x1300mm

  • Communication interfaces

    RS485/CAN

  • Communication protocols

    Modbus-RTU

  • Operating Temperature Range

    -30-50℃

  • Max. Working Altitude

    3000m

  • Weight

    3,500Kg

  • Quantity

    10

DC Side Option (2)
  • Container Option

     

  • Nameplate Energy

    3.44MWh

  • Dimension (W×H×D)

    6058×2896×2438mm

  • Communication interfaces

    RS485/CAN/Ethernet

  • Communication protocols

    Modbus-RTU/ModbuS-TCP/IEC61850

  • Operating Temperature Range

    -30℃-50℃

  • Max. Working Altitude

    3000m

  • Weight

    34,000Kg

  • Quantity

    1